Subject : 
VP1421 bypass RS232 over HDBaseT
 
Description : 
I want to use control system like VK to send the command through RS232 of VP1421 to the monitor to control power on/off TV.
Can VP1421 support to pass RS232 over HDBaseT?
 
Solution : 
Yes, it could, but the RS232 has to be connected to VP1421 display RS232 port.  Below is the testing scenario to explain:
1. PC or VK--->RS232--->VP1421 RS232 in--->VP1421 HDBaseT out--->VE802R--->RS232 cable--->VS0201
Command: sw i01 or sw i02 to switch port of VS0201
Result:
The command will only send to VP1421 to switch the input port of VP1421, not VS0201.
It means that the RS-232 is only for controlling VP1421.

2. PC or VK--->RS232--->VP1421 display RS232--->VP1421 HDBaseT out--->VE802R--->RS232 cable--->VS0201
Command: sw i01 or sw i02 to switch port of VS0201
Result:
VS0201 could switch port successfully.
 