News
FAQ Search icon_logout FAQ View
 
Subject : 
UPS Choose: a case example
 
Description : 
I have case which uses Aten UPS, below is the information. 

Solution 1 Need Runtime 30-60 Minutes. 
Device 
1. TV 43”:  15 units = 1800 Watts 
2. LCD Monitor 24 “ : 12 units = 432 Watts 
3. PC:8 units = 2400 Watts 
4. Switch 48 Port:1 unit = 23.4 Watts 
5. VE8900T:15 umits = 46.05 Watts 
6. VE8900R:15 units = 65.7 Watts 
7. CS1794:1 unit = 3.62 Watts 

Total:4770.77 Watts 

Solution 2 Need Runtime 30-60 Minutes. 
Device 
1. VE8900T:15 Units = 46.05 
2. VE8900R:15 Units = 65.7 

Total:111.75 Watts 

Would you please advice that which UPS model and how many UPS should be used on each solutions? 
 
Solution : 
Solution 1(4770.77 Watts): Need Runtime 30-60 Minutes, I split it with 2 sets of UPS. 

Please use 2 sets of OL3000HV+(2)BP72V18AH for 4800W for 45 Min. with rounding or OL3000HV+(3)BP72V18AH for 68 Min. with rounding. 

Solution 2(111.75 Watts): Need Runtime 30-60 Minutes, OL3000HV (9AH) is enough to cover 111.75 Watts more than 60 Min.
 
Related FAQ : 
ATEN 제품과의 호환성
CE250A + CS82A 지원
CS661 Local & remote resolution
与ATEN产品的兼容性
 

Was this information helpful? Y   N  
Any commend for this FAQ? 
Thank you for your valueable comment!!!!
 
If you need more assistance, please click the button on the right (Ask Question) and one of our experts will help you